Power, Brown-Outs, and CAN Bus Faults
Half of ‘the code is broken’ reports are really electrical. Two failure families dominate: brown-outs and CAN bus problems. Both have clear signatures once you know them.
Brown-out thresholds
Section titled “Brown-out thresholds”The roboRIO uses a staged brown-out scheme to protect itself from low battery voltage. The exact second-stage threshold differs by hardware:
- On both the roboRIO 1.0 and 2.0 , when voltage drops below 6.8V the 6V rail on the PWM pins begins to drop.
- The roboRIO 1.0 enters the brown-out protection state at 6.3V (fixed): PWM outputs are disabled. WPILib motor controllers send a single neutral pulse, then the output is cut.
- The roboRIO 2.0 ’s default brown-out level (Stage 2) is 6.75V , and it is software-configurable via
RobotController.setBrownoutVoltage().
When this happens mid-match your robot goes limp for a moment and the driver swears the code froze. It didn’t – the hardware protected itself.
How to confirm a brown-out
Section titled “How to confirm a brown-out”Three independent signals:
- The DS CAN/Power tab increments the 12V fault counter by 1.
- The DS records a brown-out event in the DS log.
- The DS Log Viewer marks it with a bright orange line on the voltage graph.
How to prevent brown-outs
Section titled “How to prevent brown-outs”- Use a fully charged, healthy battery (measure resting voltage and internal resistance with a tester before each match).
- Set current limits on motors – e.g.
config.smartCurrentLimit(40)on a SPARK, orCurrentLimitsConfigswithSupplyCurrentLimiton a Talon FX -- so several mechanisms can’t all spike at once. - Ramp demand instead of slamming to full output; avoid commanding every motor to peak simultaneously.
CAN bus faults
Section titled “CAN bus faults”The CAN bus is a daisy chain; problems show up as devices going missing or comms lagging.
- High CAN utilization (CAN/Power tab >90%): too many high-rate frames. Lower status-frame periods on devices you don’t read often, or reduce excessive signal refresh rates.
- Duplicate CAN IDs : two devices of the same type with the same ID on the same bus is a hard fault – one or both behave erratically or vanish. Every device of a given type needs a unique ID; check with the vendor tools (Phoenix Tuner X, REV Hardware Client).
- A loose connection anywhere breaks the chain past that point; constructors for some pneumatics/CAN devices can even throw if the bus is disconnected at boot, so wrap them in try/catch and, more importantly, verify wiring.
- Missing termination : the CAN bus needs a 120-ohm terminating resistor at the end of the chain (the PDP/PDH provides a built-in terminator) or you’ll see flaky communication.
The discipline
Section titled “The discipline”Maintain a written CAN ID map for the whole robot, label every device, and re-run a device scan in Phoenix Tuner X / REV Hardware Client after any rewiring. Most ‘random’ CAN failures are a duplicate ID or a loose connector, and both are found in minutes with the vendor scan tools.
Key takeaways
Section titled “Key takeaways”- Below 6.8V the PWM 6V rail drops; the roboRIO 1.0 disables outputs at a fixed 6.3V, while the roboRIO 2.0 default is 6.75V (configurable) – the code didn’t crash.
- Confirm brown-outs three ways: 12V fault counter, DS log event, and the orange line in the DS Log Viewer.
- Prevent brown-outs with healthy batteries, motor current limits, and ramped (non-simultaneous) demand.
- CAN faults are usually duplicate IDs, loose connectors, missing 120-ohm termination, or high utilization – diagnose with Phoenix Tuner X / REV Hardware Client and a written ID map.